Schneider South Korea three and ELR-30RM7Q grounding relay protector

Schneider Korea Sanhe ELR-30RM7Q grounding relay protector â–  MCU-based intensive design â–  Grounding protection for electric motors and distribution systems Schneider Korea 3 and ELR-30RM7Q grounding relay protectors



China Hardware Business Network

Sanhe EOCR Co., Ltd. is Korea's largest manufacturer of motor protectors. The company was founded in 1981 by Dr. Jin Renxi (CEO of Schneider Electric Group Korea).

In 2001, in order to develop the company into a global, strategic enterprise, he joined the Schneider Electric Group of France.

EOCR's main products are electronic motor protection relays, electronic overcurrent relays, electronic undercurrent relays, electronic undervoltage relays, other protection and monitoring devices, and current transformers.




â–  MCU-based intensive design

â–  Ground protection for electric motors and distribution systems

â–  Using zero sequence current detection

â–  The TEST button provides a manual self-test function

â–  Ground current and trip delay time are adjusted separately

â–  A green LED indicates that power has been established and a red LED indicates that it has tripped




Schneider Korea Sanhe ELR technical conditions







Current setting

0.03~3A (0.03, 0.07, 0.1, 0.1, 0.3, 0.5, 1, 1.5, 2, 2.5 and 3A)

time setting

0.2~2.0 seconds (0.2, 0.4, 0.6, 0.8, 1.0, 1.2, 1.4, 1.6, 1.8 and 2.0 seconds)

Working characteristics

Definite time limit

Current signal

ZCT (Zero Sequence Current Transformer) - Zero Sequence Current Detection

Control voltage

240VAC±10%

frequency

50/60HZ

Power supply error

±5%

Time error

±5%

Contact output

5A/250VAC resistance

1-SPPT/Normal is not motivated

Rated insulation voltage

600VAC, 50/60HZ

Mechanical life

10000000 actions

Electrical life

100,000 actions

Ambient temperature

-20~60°C

environment humidity

10~85% no condensation




Dielectric strength

Enclosure - line 2kv, 50/60HZ, 1 minute

Terminal - terminal 1kv, 50/60HZ, 1 minute

Line-line 2kv, 50/60HZ, 1 minute

Electrostatic discharge

IEC6100-4-2-3

Arc spark

IEC6100-4-4-3

surge

IEC6100-4-5-3

Voltage drop and interruption

IEC6100-4-11

installation

Panel embedded installation




Schneider Korea 3 and ELR reference map / wiring diagram / installation dimension drawing

China Hardware Business Network
Http://news.chinawj.com.cn Editor: (Hardware Business Network Information Center) http://news.chinawj.com.cn

PL Flanges